CDS201 - CO2, Temperature and Humidity Room Transmitter - SPECIFICATIONS
CDS201 - CO2, Temperature and Humidity Room Transmitter - SPECIFICATIONS
by E+E Elektronik
Measuring range: CO₂
- 0...2 000 ppm
- 0...5 000 ppm
Accuracy: CO₂
- < ±(60 ppm +2 % of measured value)
- < ±(60 ppm +3 % of measured value)
Measuring Range: Humidity
- 0...100 % RH, non-condensing
Accuracy: Humidity
- ±(2.8 + 0.003 * mv) % RH (at 0...80 % RH)
- ±4.1 % RH (at >80...100 %RH)
Measuring Range: Temperature
- -30...+60 °C (-22...+140 °F)
Accuracy: Temperature
- ±0.35 °C (±0.63 °F), voltage output, RS485
- ±0.7 °C (±1.26 °F), current output
Output Analog
- 0-10 V or 4-20 mA
Output Digital
- RS485 (Modbus RTU or BACnet MS/TP)
Power Supply
- 15-35 V DC or 24 V AC ±20 %