Model |
GD-70D |
GD-70D-NT |
GD-70D-ET |
Communication |
4-20mA DC |
DC power line communication |
PoE Method |
Detection principle |
Different type depending upon sensor unit and detectable gas (see table) |
Sampling method |
Sample drawing types (auto-adjustment of flow rate) 0.5 / min +/-10% |
Display |
- Large LCD display (white backlight)
- Gas concentration
- Flow rate, communication status, Pyrolyzer status, gas detected
- Error code, content of error
|
Gas alarms |
Two alarm levels: 1st alarm – Red 2nd alarm – Red Fault alarm: Yellow |
External output |
1st, 2nd, and trouble alarms : Relay contact output for each alarm |
Self diagnostic function |
System failure, sensor failure, flow failure, communication error NT / ET / Analog |
Data logging |
Event history, alarm history, calibration history. Alarm trend (180 sec before / after 1st alarm) |
Operation temp. & humidity |
0 ~ 40ºC, 30 ~ 70% RH (non-condensing) |
Operating settings |
All operational settings are user adjustable through front panel |
Power requirements |
DC 24V+/- 10%, approx 1.5W (Max 4W including sensor unit) Note: Approx. 2.5W (Max 5W) with SGU sensor unit |
PoE standard arrangement |
Dimensions |
2.8”W x 4.7”H x 5.9”D (70W x 120H x 150Dmm) |
Weight |
Approx. 0.9kg (2.0lbs), including sensor unit |
Mounting |
Wall-mounting base plate by 2 or 3 screws |
Sampling tubing |
4 x 6mm PTFE tubing recommended. Tube fittings provided as standard accessories |
Bushing |
Cable type varies depending on communication method (Cable bushing optional) |