Tek-Clamp 1200A-100M Low Cost DIN Mount Flow Meter - SPECIFICATIONS

Tek-Clamp 1200A-100M Low Cost DIN Mount Flow Meter - SPECIFICATIONS
by Tek-Trol

MATERIAL MEASURED: Virtually all commonly used clean liquids are measurable, and liquids with a small number of tiny particles may also be applicable. Particle size should be less than 75um, and particle concentration should be less than 20,000ppm. However, liquids should contain no or minor air bubbles for the best results.

Service Compatible Liquids
Parameters Specifications
Main Unit Accuracy ±1% of Reading
Velocity ±0.03 to ±100 ft/s (±0.01 to ±30m/s)
Repeatability 0.2%
Measurement Period 0.5 Seconds
Measurement Principle Transit-time measurement principle
Display LCD with backlight. 2 x 20 letters
Output
100M Modbus RS485, 4-20 mA, Pulse
Input Two three-wire system PT100 platinum resistor input loop. For BTV process monitoring
Other Functions Automatically stores the memory of the positive, negative, net totalizer flow rate and heat quantity of the last 512 days, 128 months, 10 years
Power
100M 8 to 36VDC
Power Consumption Less than 1.5W
Environment Temperature -22 °F to 176 °F (-30 °C to 80 °C)
Environment Humidity 85% RH
Protection Class IP57 (Tek-Clamp 1200A-100M)
Transducers Clamp-On S2-type: for pipe size ½” to 4” M2-type: for pipe size 2” to 28” HS-type: for pipe size ½” to 4” HM-type: for pipe size 2” to 28” 1200A-L2: 12” to 200” 1200A-IM: 3” to 7” 1200A-IL: 3” to 12”
Protection Class IP68, can work in water with depths less than 10’ (3m)
Process Temperature -40 °F to 320 °F (-40 °C to 160 °C)
Pipe Pipe Material All metals, most plastics, fiberglass, etc.
Pipe Size ½” to 28” (15mm to 700mm)
Pipe Straight Run More than 10D for upstream, more than 5D for downstream, , where D is pipe diameter.